NX-TC3406
NX-TC3406
Manufacturer: OMRON
Condition: New and Unused, Surplus.
Overview of Omron NX-TC3406
The Omron NX-TC3406 is a 4-channel temperature control unit designed for the NX-series modular I/O system. It accepts multiple sensor input types including thermocouples (various types) and platinum resistance thermometers (Pt100, JPt100, Pt1000). The unit features isolated input circuits, PNP type 4 digital PWM outputs for heat or cool control, and supports free-running signal processing with fast conversion time of 50 ms per unit.
Key Features of Omron NX-TC3406
- Channels: 4 independent control loops with isolated analog sensor inputs.
 - Input Types: Wide range including thermocouples (B, C (WRe5-26), E, J, K, L, N, R, S, T, U, P (PLII)) and resistance thermometer inputs (Pt100, JPt100, Pt1000, 3-wire).
 - Output Type: 4 digital PNP PWM outputs, suitable for heater or cooling control.
 - Signal Processing: Free running type for asynchronous updating of measurement and control.
 - Isolation: High-level isolation between sensor inputs, control outputs, and internal circuitry (Transformer and digital isolators, photocoupler isolation).
 - Mounting: DIN rail mounting with screwless clamping terminal blocks for easy installation and maintenance.
 - Dimensions: 24 mm (W) × 100 mm (H) × 71 mm (D), weighing approximately 140 g.
 - Protection and Safety: Load short-circuit protection, input disconnection detection, and insulation resistance ensure reliable and safe operation.
 - Power Supply: Supplied from the NX bus, with 0.55 to 1.75 W power consumption depending on connection.
 - Operating Environment: 0 to 55°C ambient temperature range with 10 to 90% humidity (non-condensing).
 
Technical Specs of Omron NX-TC3406
| Model | NX-TC3406 | 
|---|---|
| Number of Channels | 4 | 
| Input Types | Thermocouples (B, C, E, J, K, L, N, R, S, T, U, P), Pt100, JPt100, Pt1000 (3-wire) | 
| Output Type | 4 PNP digital PWM outputs | 
| Conversion Time | 50 ms per unit (per channel) | 
| Isolation | Power: Transformer; Signal: Digital isolator; Output: Photocoupler isolation between outputs and internal circuit | 
| Dimensions (W×H×D) | 24 × 100 × 71 mm | 
| Weight | 140 g | 
| Power Supply | NX Bus provided | 
| Operating Temperature | 0 to 55 °C | 
| Humidity | 10% to 90% (non-condensing) | 
| Indicators | TS indicator, output indicators | 
Applications / Use Case
The NX-TC3406 is tailored for precise multi-channel temperature control in industrial automation, especially in processes requiring robust sensor integration, fast and stable control outputs, and easy system expansion within the NX-series I/O architecture.
Verification Links:
https://industrial.omron.eu/en/products/NX-TC3406
https://www.omron-ap.com/products/family/3699/specification.html
https://www.mouser.com/ProductDetail/Omron-Automation-and-Safety/NX-TC3406
                    
                      
                      
                        Price Matching / Price on Inquiry
                      
                    
                    
                  
                  Price Matching / Price on Inquiry
If this item is readily available at a lower price through any valid distributor, please contact us for price matching. Leadtime is committed to providing you with the best value for your purchase.
                    
                      
                      
                        Warranty
                      
                    
                    
                  
                  Warranty
Leadtime offers a 1-year warranty for all products sold and repaired, providing a dependable and reliable investment in your company's future.